From Health 201FailSystems

how automated healthcare fails, how you'd know, and what to do at each tier — every claim sourced, reviewed continuously


Incident

Superstorm Sandy: NYU Langone and Bellevue lose backup power and evacuate

Storm surge flooded basements holding fuel tanks and pumps at two Manhattan hospitals whose generators sat on upper floors. Both hospitals evacuated.

Sources checked when written 26 September 2026

TierFlooding reached the fuel systems for the backup generators; NYU Langone evacuated about 300 patients and Bellevue more than 700. How tiers are assigned.

What happened

NYU Langone's generators were on upper floors, but the surge breached a basement vault holding its fuel system; the hospital evacuated about 300 patients, including 21 neonates moved out of the NICU in 4.5 hours. Bellevue's generators were also high up, but fuel pumps and tanks were in a basement that took an estimated 17 million gallons of water; AP reported more than 700 patients evacuated. HHS OIG's review of 172 hospitals in the declared area found 69 lost utility power and, for 28 of them, backup generators were not reliable. It describes one hospital (photo credited to NYC Health and Hospitals Corporation) where staff passed fuel up 13 flights of stairs in a 'bucket line' because the pumps were flooded, and where staff decided in advance which machine-dependent patients would keep the few emergency outlets.[1,2,3]

Documented harm

No patient deaths attributed to these evacuations in the sources reviewed. OIG documents patients arriving at receiving hospitals without medical records.

What it teaches

Sources

  1. What caused generators to fail at NYC hospitals?. CBS News / Associated Press, 2 November 2012. Secondary Journalism · link checked 2026-09-26
  2. Evacuation of a neonatal intensive care unit in a disaster: lessons from Hurricane Sandy. Pediatrics (American Academy of Pediatrics), 2014. Primary Peer-reviewed · link checked 2026-09-26
  3. Hospital Emergency Preparedness and Response During Superstorm Sandy (OEI-06-13-00260). US HHS Office of Inspector General, 16 September 2014. Primary Official report · link checked 2026-09-26

All incidents · Power · Cascades · Devices · Human handoff

Information only, not advice. FailSystems is an aggregation and synthesis of published sources. It is not consulting, engineering, legal, regulatory or medical advice, and using it creates no professional relationship. Health systems are complex and no approach fits every organisation: anything you adopt is your own decision, at your own risk, and should be checked against the current official sources and by qualified people who know your setting. Full disclaimer.

Dealing with an incident right now? This site is a reference, not an incident-response service. Activate your organisation's emergency operations plan and incident command, and: