Incident

Faulty extension cord cuts power to Sabah hospital operating theatres; UPS fault keeps the generator from taking over

In a statement on 19 November 2026, the Sabah Health Department (JKNS) said a faulty extension cord caused a power disruption in the operating theatres of Sabah Women and Children's Hospital on 13 May 2025. It said the UPS did not work and the emergency generator did not take over.

Sources checked when written 28 November 2026

TierJKNS, as reported, says the theatres lost power, the UPS failed and the generator did not take over, which is loss of power without working backup, confined to the operating theatres. How tiers are assigned.

What happened

According to the JKNS statement as reported by The Star (via Bernama), a faulty extension cord caused a power disruption in the operating theatres of Sabah Women and Children's Hospital (HWKKS) on 13 May 2025, and an internal fault in the UPS system also prevented the emergency generator from operating. Sabah Media's Malay-language report of the JKNS statement does not name the hospital or the date. It describes the chain this way: a damaged extension cable was identified as the cause; the main circuit breaker at the sub-main switchboard tripped; the UPS at the general operating theatre (Dewan Bedah Am) then stopped working, and the generator did not take over automatically. Neither report says how long power was out, whether an operation was under way, or what happened to patients. JKNS said the Health Ministry had issued a directive banning extension cords in hospitals and told all hospitals to remove any still in use. It said it had instructed its hospital support services concessionaire to step up monitoring of generators, UPS systems, electrical distribution panels and critical medical equipment in operating theatres. The Star names the concessionaire as Sedafiat Sdn Bhd. Sabah Media says UPS replacement projects have been carried out at hospital level. On 17 November 2026, two days before the statement, Wangsa Maju MP Zahir Hassan told the Dewan Rakyat that a doctor at an unnamed Sabah hospital had to stitch up a patient by phone flashlight during a power failure. He said the absence of a functioning UPS contributed. The Star reported no ministry response, and Sabah Media reports that the Malaysian Medical Association urged the ministry to investigate. None of these sources says whether the MP's claim concerns the HWKKS incident.[1,2,3,4,5,6,7]

Documented harm

none documented; the JKNS statement as reported does not describe the effect on patients

What it teaches

  • A fault on one local circuit can trip an upstream breaker and take out the UPS that the generator changeover depends on, so backup tests should cover the full fault-to-transfer path, not only generator start.
  • A ban on extension cords in clinical areas only works if someone checks it is being followed, because improvised wiring sits outside the designed electrical protection.

Sources

  1. Faulty extension cord cause of 2025 power disruption at Sabah hospital. The Star (Bernama), 19 November 2026. Secondary Journalism · link checked 2026-11-28
  2. 'Extension cable' rosak punca gangguan elektrik dewan bedah - JKNS. Sabah Media, 20 November 2026. Supporting Journalism · link checked 2026-11-20
  3. Sabah doctor stitched up patient with phone flashlight during operation due to power failure, Parliament told. The Star, 17 November 2026. Secondary Journalism · link checked 2026-11-28
  4. Sabah doctor forced to operate by flashlight? MMA shines spotlight on Health Ministry. Malaysiakini, 19 November 2026. Secondary Journalism · link checked 2026-11-28
  5. MMA seeks urgent probe into claim Sabah doctor used phone torch during procedure. The Vibes, 19 November 2026. Supporting Journalism · link checked 2026-11-28
  6. Power, water woes at Sabah's govt hospitals must be addressed seriously, says consumer group. The Star, 21 November 2026. Secondary Journalism · link checked 2026-11-28
  7. Call to probe Sabah hospital blackout. The Star, 21 November 2026. Secondary Journalism · link checked 2026-11-28

Main generator at Gaza's Al-Rantisi children's hospital stops; Health Ministry says vital services halted and a smaller generator cannot cover intensive care

On 25 November 2026 the Ministry of Health in Gaza said the main generator at Al-Rantisi Children's Hospital had stopped suddenly, halting a number of vital medical services and, according to Anadolu's Arabic report, the operating rooms of the neighbouring Eye Hospital. The ministry said repairs were hampered by a complete absence of oils and spare parts.

Lexington, Massachusetts nursing home evacuated after recurring electrical failure; building de-energised

On the night of 24 October 2026 more than 100 residents were evacuated from a nursing and rehabilitation centre in Lexington, Massachusetts, after electrical problems that had recurred over several days. Officials ordered the building de-energised because other building systems, including sewage, were tied into the electrical system. Residents had returned by mid-November, Boston 25 News reported.

Power interruptions at the SPMS data centre take Portugal's national e-prescribing and electronic health record offline

On 19 October 2026, two successive power interruptions at the data centre run by SPMS, the Ministry of Health's shared-services body, left SNS information systems unavailable for several hours. Doctors could not issue electronic prescriptions or consult electronic records, and pharmacies had limited access to prescriptions.

PathPower → Connectivity & data

Two power outages knock out Kemptville hospital's EHR, internet and cellular service and their backups; ambulances diverted

On 13 October 2026 two power outages knocked out Kemptville District Hospital's cellular service, internet, electronic health record and its downtime and backup systems. The hospital declared a code grey, moved to paper, asked lower-acuity patients to go elsewhere and diverted ambulances.

PathPower → Connectivity & data → Human handoff

Prague Central Military Hospital: power cut and failed backup pause operations

Doctors told Seznam Zprávy that a power cut at Prague's Central Military Hospital, which backup generators did not adequately cover, paused all operations for about 20 minutes and left ventilators running on internal batteries. The hospital said the interruption lasted several minutes and did not affect patients' health.

All incidents · Power

Information only, not advice. FailSystems is an aggregation and synthesis of published sources. It is not consulting, engineering, legal, regulatory or medical advice, and using it creates no professional relationship. Health systems are complex and no approach fits every organisation: anything you adopt is your own decision, at your own risk, and should be checked against the current official sources and by qualified people who know your setting. Full disclaimer.