Air conditioning tripped at both trust data centres on the UK's record-heat day. Clinical IT went down and the trust ran on paper for weeks.
TierData-centre cooling failed and the trust ran a 'Paper Hospital' for about six weeks; clinical areas kept power. How tiers are assigned.
On 19 July 2022 (London peaked at 40.3°C) condenser high-pressure trips shut down cooling at the Guy's data centre, which reached 50.3°C; the St Thomas' data centre suffered disk and controller failures. The two sites were each other's backup, a design the trust's review said could not cover a shared environmental cause. Cooling concerns had been raised in 2018 and a £195k replacement request from March 2022 was still unapproved. The remote environment monitoring for St Thomas' was hosted on the storage network that failed, and email alerts stopped. The trust declared a critical incident and moved to a 'Paper Hospital'. Core clinical systems took about six weeks to recover, slowed by 371 interlinked systems. Activity fell to 64% of normal referrals and 68% of diagnostic tests. The same heat caused a cooling failure in a Google Cloud London zone that day.[1,2]
As of January 2023: one moderate harm (a patient could not be transplanted when organs became available), 20 low harms, no deaths or severe harm identified; the harm review remained open.
All incidents · Power · Connectivity & data · Cascades
Information only, not advice. FailSystems is an aggregation and synthesis of published sources. It is not consulting, engineering, legal, regulatory or medical advice, and using it creates no professional relationship. Health systems are complex and no approach fits every organisation: anything you adopt is your own decision, at your own risk, and should be checked against the current official sources and by qualified people who know your setting. Full disclaimer.